TM 10-6640-215-13
Alphabetical Index - continued
Maintenance Item
Paragraph
Water Heater ..................................................... ..................................................................................
5-12
Water Pump .........................................................................................................................................
5-5
Water Tank ......................................................... .................................................................................
5-6
Water Tank Drain .................................................................................................................................
5-7
5-4.
INTRODUCTION.
a.
This section contains instructions covering maintenance functions for direct support level maintenance on the
Petroleum Laboratory. Personnel required are listed only if the task requires more than one.
b.
After completing each maintenance procedure, perform operational check to be sure that equipment is
properly functioning.
5-5.
REMOVE/INSTALL WATER PUMP.
This task covers:
a.
Removal
b.
Installation
INITIAL SETUP:
Tools required
General Mechanics Tool Kit, (Appendix B, Section III, Item 2)
Material Required
Teflon Tape, (Appendix E, Section II, Item 157)
General Safetv Instructions:
WARNING
ELECTRICAL SHOCK
Before performing any maintenance actions on electrical equipment, ensure all electrical power
has been turned off. Death or serious injury may occur from failure to do this.
REMOVAL
Remove Water Pump. See figure 5-1.
a.
Set switch on WATER PUMP controller to OFF.
b.
Set A15CB8 at POWER PANEL No. 2 to OFF.
c.
Tag for reconnection and disconnect pump motor electrical leads at motor connection box.
d.
Disconnect union on pump discharge line to the surge tank.
e.
Disconnect union on suction supply line from water filter.
f.
Disconnect hose from drain petcock.
g.
Remove four bolts, nuts, flat washers, and lockwashers that secure pump to foundation.
h.
Remove water pump.
5-2
|
|