Custom Search
 
  
 


TM 9-2330-329-14&P
OPERATION UNDER USUAL CONDITIONS--Continued
0007 00
h.
After flow has begun, set valve D (8) to the closed position to precheck automatic shut off. If
shut off is functional, flow should stop after 2025 seconds. Open valve D (8); flow should
resume in 20 seconds.
WARNING
If fuel flow into semitrailer stops because of a shut off
malfunction, or the presence of leaks, or if any other
unusual conditions are observed, stop fuel supply at
loading facility and notify your supervisor.
i.
When tank is full, flow will stop automatically.
j.
Shut off engine.
k.
Drain hose (2) into suitable container.
l.
Close all valves and vapor system vent caps.
m.
Remove and store hose (2) in hose tubes (3).
n.
Remove grounding cables.
o.
Store and cover fire extinguishers (1).
Self-Loading Flow Chart
0007 00-20



 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business