TM 10-6640-215-13
Table 4-2. Troubleshooting- continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
NO POWER AVAILABLE IN PETROLEUM LABORATORY (PURGE CYCLE TOOK PLACE AND CIRCUIT
BREAKER AICBI PLACED IN ON POSITION).
Reset circuit breaker A1CB1.
If power still not available, replace circuit breaker A 1CB1. See paragraph 4-19.
5.
A GROUP OF CEILING LIGHTS FAILS TO OPERATE (ALL OTHER CEILING LIGHTS OPERATE).
Step 1.
Check that power is available at appropriate wall light switch.
a.
If power is available, replace switch. Refer to paragraph 4-23.
b.
If power is not available, proceed to step 2.
Step 2.
Check and reset appropriate circuit breaker.
If power still not available, replace circuit breaker. See paragraph 4-19.
6.
DOOR INTERLOCK (MICRO) SWITCH DOES NOT OPERATE PROPERLY.
Step 1.
Check switch electrical connections.
Step 2.
Adjust switch.
If switch still fails to operate properly, replace the door interlock switch. See paragraph 4-24.
7.
CONVENIENCE OUTLET (RECEPTACLE) INOPERATIVE.
Step 1.
Check that power is available at outlet.
a.
If power is available, replace outlet. See paragraph 4-25.
b.
If power is not available, proceed to step 2.
Step 2.
Check and reset appropriate circuit breaker.
If power is still not available, replace circuit breaker. See paragraph 4-19.
8.
A/C (ECU) REMOTE CONTROL UNIT FAILS TO OPERATE PROPERLY (POWER AVAILABLE).
Troubleshoot in accordance with TM 5-1420-371-14. If necessary, replace faulty remote control unit. See
paragraph 4-26.
4-14
|
|