Custom Search
 
  
 


TM 9-2330-329-14&P
VAPOR INTEGRITY TEST--Continued
0152 00
CAUTION
Although an emergency valve leak does not constitute a
K stamp (indicating compliance with DOT 49CF180.407 (h))
failure if the leak is internal, proper emergency valve operator
function is required for safe operation.
8.
Close emergency valve A (25) and monitor gage (30) on regulator assembly (12).
9.
Wait 5 minutes to verify that pressure reading remains stable. If pressure drops more than 0.5 in.
wc on gage (30), go to step 10. If pressure remains at 17.5 to 18.5 in. wc, go to step 13.
0152 00-5



 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business