Purge System and Gas Alarm Controls and Indicators. Figure 2-6 and Table 2-6 list the controls and indicators
of the purge system and gas alarm system.
Table 2-6. Purge System and Gas Alarm Controls and Indicators
Index
Number
Control or Indicator
Function
1
Detector Selector Switch
In AUTO mode meter responds to channel with strongest signal.
Turned to channel 1 or channel 2 position meter responds to
signal from selected channel.
2
Indicator Meter
Indicates concentration of combustible gas at detection point.
3
Gas Alarm Pilot Light, Green
Indicates gas alarm power is on and detector circuit is energized.
4
Alarm Indicators
Illuminates to indicate which remote detector an alarm condition is
present at. Light goes out when alarm reset switch is pressed
and no alarm conditions remains.
5
Warning Indicators
Illuminates to indicate which remote detector a warning condition
is present at. Light goes out when alarm reset switch is pressed
and no warning conditions remains.
6
Fail Indicators
Illuminates to indicate which remote detector a fail condition is
present at. Light goes out when alarm reset switch is pressed
and no fail conditions remains.
7
Alarm Reset Switch
When pressed, deactivates holding circuits of alarm and warning
relays if a safe gas condition has been restored at remote
detector. If a safe condition does not exist, unit cannot be
reset.
8
Warn/Test Light, Yellow
Indicates combustible gas condition exceeding low alarm setting
exists at remote detector, or when alarm test switch has been
activated. When pressed, provides a simulation of an alarm
level of gas concentration at remote detector. Also provides a
functional check of the analyzer and remote alarm circuit.
9
Gas Alarm Fail Light, Blue
Indicates gas alarm failure or malfunction.
10
Gas Alarm Light, Red
Indicates combustible gas warning
11
Purge Doors Limit Switches
Provides signal to purge alarm buzzer if one of purge doors is not
opened when purge cycle is initiated.
|
|