TM 10-6640-238-13
2-3
b.
Power Panel Assemblies. Figure 2-2 and 2-3 and Tables 2-2 and 2-3 list the circuit breakers located in Main
Power Panel and Power Panel No. 2.
Table 2-2. Main Power Panel Controls and Indicators
Index
Number
Control or Indicator
Function
1
A1CB1
Main circuit breaker. Provides 225A circuit protection for main power
input. In the ON position, applies power to all system circuit breakers.
2
A1CB3
Provides 20A circuit protection for JFTOT and Utility No. 7.
3
A1CB5
Provides 15A circuit protection to Ovens and Utility No. 4.
4
A1CB7
Provides 20A circuit protection to Distillation Units.
5
A1CB9
Provides 15A circuit protection for Phase A, rear laboratory overhead
lights.
6
A1CB11
Provides 15A circuit protection for Phase B, front laboratory overhead
lights.
7
A1CB13
Provides 15A circuit protection for Phase C, blackout lights, three
overhead lights (just forward of rear door) and gum bath and fume hood
wall switch.
8
A1CB15
Provides 30A circuit protection for Oxidation Stability Bath and wall
switch.
9
A1CB17
Provides 15A circuit protection for Water Heater.
10
A1CB19
Provides 15A circuit protection for Steam Super Heater (High Pressure
Boiler).
11
A1CB21
Provides 20A circuit protection for Outside Receptacle (GFI).
12
A1CB22
Not Used
13
A1CB20
Provides 15A circuit protection for Fume Hood Utility Receptacle.
14
A1CB18
Provides 30A circuit protection for Gum Bath.
15
A1CB16
Provides 15A circuit protection for RVP Bath and Utility No. 5.
16
A1CB14
Provides 15A circuit protection for the Sump Pump.
17
A1CB12
Provides 20A circuit protection for Muffle (Burnout) Furnace.
18
A1CB10
Provides 15A circuit protection for Utility No. 6.
19
A1CB8
Provides 15A circuit protection for Centrifuge, Freezer, and Utility No.
2 in mechanical room.
20
A1CB6
Provides 15A circuit protection for Refrigerator and Utility No. 3.
21
A1CB4
Provides 20A circuit protection to Viscosity Bath.
22
A1CB2
Provides 100A circuit protection for power input to Power Panel No. 2.
|
|